GF Piping Systems

GF Piping Systems PVDF In-Rack Liquid Cooling Manifold

Official Georg Fischer Piping Systems In-Rack Manifold fact sheet, opened 18 November 2026, describes a custom-PVDF manifold for direct liquid cooling. Official technical data: pressure rating PN10; material PVDF; colour opaque; temperature range −20 °C to 80 °C (−4 °F to 176 °F); official flammability standard UL 94 V-0 (manufacturer wording, not a YOCOOLING certification); inner surface Ra < 0.5 μm (20 μin) for injection-moulded and extruded components; capped ports; configuration top or bottom feed; options include dimension, length, ports and quick disconnects, with optional air bleeder, draining or special ports. Official quality-control wording: 100% pressure tested with water before shipment; official “system lifetime 25 years” is manufacturer wording, not a YOCOOLING warranty. The official illustration of a 132 kW, 48U, 48-outlet example at about 6 L/min per outlet with PG25 is a manufacturer design example, not this page’s configuration and not a YOCOOLING performance guarantee. The fact sheet states that its technical data are not binding unless confirmed in writing and do not constitute warranted characteristics; that is manufacturer wording. Send the required rack geometry, port map, connections and quantity to enquire. Official source: https://www.gfps.com/content/dam/gfps/com/brochures-and-flyers/en/gfps-datasheet-in-rack-manifold-en.pdf This page is not a stock, price or warranty statement.

Material
PVDF
Mounting
top feed; bottom feed
Pressure designation
PN10 1
Temperature range
maximum: 80; minimum: -20 °C 2
Request a Quote

GF Piping Systems PVDF In-Rack Liquid Cooling Manifold

GF Piping Systems PVDF In-Rack Liquid Cooling Manifold

Specifications

ParameterValue
GF in-rack manifold
MaterialPVDF
Mountingtop feed; bottom feed
Integrated componentsmain connections; branch ports; quick disconnects; optional air bleed; optional drain
Test conditions100% pressure tested with water before shipment; acceptance pressure/time are not stated in the sheet and must be agreed.
PVDF in-rack manifold / factsheet 04.26
Pressure designationPN10 1
Temperature rangemaximum: 80; minimum: -20 °C 2
PVDF in-rack manifold / M1161 quote sheet
Geometry rfq inputsMaximum length, available width/depth, outer diameter, outlet count, initial port offset u0 and subsequent spacing u1; attach a drawing for non-uniform spacing. 3
Connection rfq inputsSpecify the exact quick-disconnect interface, nominal diameter and thread connection; listed supplier alternatives do not imply cross-brand interchangeability. 4
Feed and service optionsTop or bottom feed, straight or 90-degree feed geometry, orientation, end cap, vent or drain; define the installed routing. 5
Specifications
Official series documentGF In-Rack Manifold fact sheet, opened 18 November 2026 (custom-series, not a single stock SKU)
Official material and ratingPVDF; PN10; official temperature range −20 °C to 80 °C; colour opaque
Official configuration optionsTop or bottom feed; official options include dimension, length, ports and quick disconnects; optional air bleeder, draining or special ports
Official quality-control wording100% pressure tested with water before shipment (official fact sheet). Official “system lifetime 25 years” and UL 94 V-0 are manufacturer wording, not a YOCOOLING warranty or certification.
Notes 5
  1. Nominal designation; allowable pressure depends on temperature, coolant and final assembly. Page 2 derating curve applies.
  2. Datasheet temperature limits are not a rectangular PN10 operating envelope; consult page 2 pressure-temperature curve.
  3. Required design inputs, not fixed catalog dimensions
  4. Manufacturer blank quote form options; compatibility still requires matching interface drawings