Danfoss · DST P140
Danfoss DST P140 MEMS Pressure Transmitter
SeriesDST P140
DST P140 is a MEMS pressure-transmitter series for liquid-cooling data centers. Range, signal and connections depend on the selected configuration.
Configuration shown: 075G4027
- Gauge pressure range
- 0 to 10 barMeasuring range; not an overpressure rating.
- Output signal
- 4 to 20 mA
- Supply voltage
- 8 to 28 VDC
- Wetted materials
- AISI 304L and AISI 316L listed for wetted partsConfirm coolant and seal compatibility for the application.
Specifications
| Parameter | Value |
|---|---|
| Danfoss DST P140 pressure transmitter series | |
| Application | Liquid-cooling data-center pressure monitoring |
| Sensing and body design | MEMS sensing technology with stainless-steel design and hermetically sealed media interface |
| Diagnostic option | Automatic sensor-failure detection (optional) |
| Danfoss DST P140 075G4027 | |
| Gauge pressure range | 0 to 10 barMeasuring range; not an overpressure rating. |
| Output signal | 4 to 20 mA |
| Process and electrical connections | G 1/4 A male pressure connection to ISO 1179-2; M12 × 1 electrical connectionMating connector is selected separately. |
| Supply voltage | 8 to 28 VDC |
| Wetted materials | AISI 304L and AISI 316L listed for wetted partsConfirm coolant and seal compatibility for the application. |
| Specifications shown for 075G4027. Other DST P140 variants use different ranges or connections. | |
| Specifications | |
| Official series documents | DST P110 / DST P140 for Data Center Liquid Cooling, AI570944104418en-000102, opened 18 November 2026; product page also opened the same day |
| Official ordering note | Contact Danfoss for dedicated data-center code numbers; this page does not assign a store SKU |
| Official total error band (series) | ±0.5 % FS (20 °C − 60 °C), as stated in the official datasheet; FS = full scale |
| Official response time (series) | < 2 ms (official datasheet) |
| Official overload / burst (series) | Overload 4 × FS; burst 300 bar (absolute / sealed gauge) or 5 × FS (relative gauge). These are official series figures, not a selected code. |
| Official output options (series) | 4 − 20 mA, or ratiometric (10 – 90% Vss); exact output follows the official code |
| OCP wording | Official datasheet wording: “UL recognized and aligned with OCP recommendations.” Manufacturer wording only; not a YOCOOLING certification or OCP claim. |
| Official datasheet URL | https://assets.danfoss.com/documents/latest/601238/AI570944104418en-000102.pdf |
| Official product page URL | https://www.danfoss.com/en/products/sen/sensors-and-transmitters/industrial-pressure-transmitters/dst-p140-pressure-transmitter-for-water-and-air-applications/ |