SMC
SMC FC2W520-04-3-X110 Automatic Water Flow Controller
Manufacturer part numberFC2W520-04-3-X110
Official SMC FC2W-X110 catalog (15-E663) opened 18 November 2026 lists FC2W520-04-3-X110 as a water flow controller: Karman-vortex detection, 2.0 to 16.0 L/min control range, 1.6 to 16.8 L/min measurement range, Rc 1/2 port, 3 m lead with connector, 0.2 to 0.4 MPa operating pressure at 0 to 50°C fluid temperature, 0.6 MPa withstand pressure, ±5% F.S. control accuracy, response 10 s or less, analogue voltage input 1 to 5 VDC, flow-rate pulse output, 24 VDC ±10%, and 530 g. Leakage when fully closed is 1 L/min or less; a shutoff function is not provided, and the catalog requires an external shutoff valve to stop flow in an emergency. Wetted materials listed: PPS, PP, POM, FKM, stainless steel 303, stainless steel 304, SCS13, non-grease. Applicable fluid is water; glycol compatibility is not inferred. Send the exact official part number and control-interface details to enquire. This page is not a stock list.
Specifications
| Parameter | Value |
|---|---|
| SMC FC2W520-04-3-X110 | |
| Ordering code | FC2W520-04-3-X110; 1/2 in. Rc port; 3 m lead 1 |
| Rated flow control range | 2.0–16.0 L/min 2 |
| Process port | Rc 1/2 3 |
| Working pressure | 0.2–0.4 MPa at 0–50 °C fluid temperature; proof pressure 0.6 MPa 4 |
| Control accuracy | ±5% F.S. flow-control accuracy; response time ≤10 s 5 |
| Power and signal | 24 VDC ±10%; analogue voltage input 1 to 5 VDC (official catalog); flow-pulse output 6 |
| Medium and temperature | Water; fluid temperature 0–50 °C without freezing 7 |
| Shutoff limitation | Controller cannot fully close; an external shutoff valve is needed for emergency stop 8 |
| Specifications | |
| Official FC2W-X110 catalog | https://ca01.smcworld.com/catalog/New-products-en/mpv/15-e663-fc2w/data/15-e663-fc2w.pdf (opened 18 November 2026; English catalog 15-E663; model column FC2W520-04-3-X110) |
| Official input signal (correction) | 24 VDC ±10%; analogue voltage input 1 to 5 VDC (official catalog); flow-pulse output 6 |
| Official flow measurement range | 1.6 to 16.8 L/min 9 |
| Official leakage when fully closed | 1 L/min or less 10 |
| Official wetted materials | PPS, PP, POM, FKM, stainless steel 303, stainless steel 304, SCS13; non-grease specifications 11 |
| Official weight | 530 g 12 |
Notes 12
- Exact catalogue ordering example
- medium: Water; catalogue specified operating conditions
- Confirm mating thread and line size in quote
- Proof pressure is not the normal working range
- Catalogue condition; not a fast-acting safety shutoff
- official catalog for FC2W520-04-3-X110; earlier 0–5 VDC wording was not the official input range
- Do not infer glycol or other coolant compatibility from water rating
- Functional boundary of FC2W-X110 series
- official catalog measurement range for FC2W520-04-3-X110; distinct from the 2.0 to 16.0 L/min control range
- official catalog note; a shutoff function is not provided. Use an external shutoff valve to stop flow in an emergency, as the catalog states.
- official catalog list for parts in contact with fluid
- official catalog value for FC2W520-04-3-X110