Official Envicool “Liquid Cooling Quick Disconnect” datasheet, opened 18 November 2026, describes the CGB series as a flat-face coupling with no locking mechanism, locked through an external fastener, and official wording that the correction capability can compensate for a maximum misalignment error of ±1.5 mm (this official CGB figure is not the MQDB ±1 mm figure). Official technical performance includes working temperature −55 °C to +120 °C, working pressure 0 to 100 psi, shell material SUS316L/EPDM, sealing-ring options EPDM and FVMQ, and official endurance 5000 mating cycles. Official product codes are configuration examples, not a stock list. Send the official product code, retention method, ends, coolant and quantity to enquire. Official source: https://en.envicool.com/upload/file/20250928/1759043053359138.pdf
Specifications
| Parameter | Value |
|---|---|
| CGB series | |
| Retention | No integral lock; externally fastened 1 |
| Alignment allowance | plus or minus 1.5 mm 2 |
| Size specific recommended flow | CGB03 2.1; CGB05 5.9; CGB08 15.1; CGB12 33.9 L/min 3 |
| Material choices | Aluminum-alloy and stainless-steel part-code columns 4 |
| Size specific socket plug end examples | For CGB03, the order tables separately list G1/8 male-thread socket CGB03.1342-G18 and plug CGB03.7342-G18 in stainless-code columns; alternate ends and body materials have other codes 5 |
| Seal options | CGB series summary lists EPDM and FVMQ sealing-ring options; the selected order code and coolant compatibility must be verified. 6 |
| Series pressure temperature reference | CGB series summary lists working pressure 0–100 psi and working temperature -55 to +120 °C; the selected pair, seal and coolant require configuration review. 7 |
| Specifications | |
| Official series document | Envicool Liquid Cooling Quick Disconnect datasheet, opened 18 November 2026 |
| Official lock and alignment | No integral lock; locked through an external fastener; official maximum misalignment compensation ±1.5 mm (manufacturer figure; not the MQDB ±1 mm figure) |
| Official series performance | −55 °C to +120 °C; 0 to 100 psi; SUS316L/EPDM; official sealing-ring options EPDM and FVMQ; official endurance 5000 mating cycles (manufacturer figures) |
Notes 7
- blind-mate structure requires equipment-level retention
- manufacturer series claim; validate exact size, mounted stack and stroke
- separate model rows, water 20 degC, plug-to-socket, 5 m/s velocity criterion; CGB10 appears in ordering table but not this flow row
- material depends on exact code; seal and all wetted material need verification
- Example series pair; verify mounted geometry, material, seal and selected mating halves
- Manufacturer series options, not proof of the part's installed seal
- Manufacturer series summary; not a combined end-code and coolant approval